• Four-digit green LED display with 100 mm symbol height.
  • Measurement and conversion of electrical signals generated by thermocouples, RTDs, and sensors with DC-current output.  
  • Three-wire or four-wire RTD connection.
  • Device conversion function – linear or square-root extracting.
  • Cold junction temperature compensation (internal sensor).
  • The configurable analog input.
  • Continuous sensor fault detection.
  • Programmable DC-current output 0..5, 0..20 or 4..20 mA.
  • Interface RS-485, protocol Modbus (RTU).

 

Technical specifications

Thermocouples K, L, S, B
RTDs:

  •  platinum (W100=1.3850 и W100=1.3910)
  •  copper (W100=1.4260 и W100=1.4280)
 

Pt50, Pt100, Pt500

Cu50, Cu100 

DC-current input signal range, mA 0..5; 0..20; 4..20
Temperature measurement error (for thermocouples), °С:

  • L, K in the range of -150..0°С
  • L, K in the range of 0..800 (1300)°С
  • S, B

±(0.25·10-2×|t|+2.5)
±(0.1·10-2×|t|+2.5)
±7.0

Temperature measurement error (for RTDs), °С ±(0.2·10-2·(t+273)+0.1)

Reduced DC-current signal measurement error, %:

  • for input signal range 0..5 mА
  • for input signal range 0..20, 4..20 mА

±0.5
±0.25

DC-current output error, mA ±0.05
Baud rate,  Kbps 9.6; 19.2; 38.4
Least significant digit value 0.001; 0.01; 0.1; 1
Supply voltage 220VAC 50Hz
Operating temperature range +5°С..+50°С
Protection type (IP code) IP41
Size (W×H×D), mm 430×210×85

   

Ordering designation

Digital measuring device  IP-6-TK-U

Device is equipped with a remote console for device setting up.