- Developed for replacement of widely applied differential-transformer sensors.
 - Can be used for measuring rotor’s axial shift, rotor’s differential expansion (axial growth), rotor deflection, case thermal expansion, valve position, servomotor stroke and other displacements.
 - Contactless conversion of collar linear displacement relative to the working surface of the VDP into three output electrical signals.
 - Produced for nominal collar thickness 8, 18, 24, 32, 140 mm.
 - Can be produced for any nominal collar thickness on request.
 - Listed in the State Register of Measurement Instruments of Ukraine as a part of meter IK-1-TK-1.
 - Complies with requirements of technical conditions TU U 33.2-32436145-002:2008.
 
Technical specifications
| 
 Measuring range L: L=1.75×Dn, mm where Dn – nominal collar thickness for sensor, mm.  | 
|
| 
 When using the digital measuring device IP-1-TK it is allowed to use collars with unnominal thickness. For collars with thickness from Dn/2 to 2×Dn measuring range L: L=1.5×Dn+(Dn – Du), mm where Du – selected collar thickness, mm. For collars with thickness more then 2×Dn measuring range L: L=1.5×Dn, mm.  | 
|
| 
 Linear displacement to electric signal conversion error, mm: ±(0.02×Dn+0,01×|Dn – Du|)  | 
|
| 
 Operating temperature range  | 
 -10°С..+100°С  | 
| 
 Operating temperature range for special make  | 
 -10°С..+150°С  | 
| 
 VDP and collar rated clearance, mm*  | 
 0.5..2.8  | 
| 
 Current consumption, mA  | 
 400  | 
| 
 Supply voltage  | 
 7.5VAC 50Hz  | 
| 
 Protection type (IP code)  | 
 IP67  | 
| 
 Size (W×D×H), mm: 
  | 
 42×42×85 91×59×80 142×56×103 174×56×103 640×68×125  | 
* – depends on the VDP model and collar type
Ordering designation
Vector displacement sensor VDP–XX–YY–Z–Q:
XX – nominal collar thickness;
YY – measuring range using nominal thickness collar;
Z – VDP location relative to the turbine casing:
«P» – VDP connector is located at the top right or bottom left of the turbine casing;
«L» – VDP connector is located at the top left or bottom right of the turbine casing;
Q – VDP enclosure:
«U» – redundance enclosure;
no marking – standard enclosure.
Example . Vector displacement sensor VDP-24–42-P-U – VDP at redundance enclosure for collar with 24 mm nominal thickness, measuring range using nominal thickness collar 42 mm; acceptable collar thickness from 12 mm till 48 mm; VDP connector is located at the top right or bottom left of the turbine casing.