Измеритель линейных премещений, ОСР ИП-5-ТК
  • Mechanical measurements: rotor’s axial shift and rotor’s differential expansion (axial growth), other displacements, measured by the sensor with DC-current output.
  • Complies with requirements of technical conditions TU U 33.2-32436145-002:2008.
  • Listed in the State Register of Measurement Instruments of Ukraine. 
  • Single or dual sensors connection.
  • Provides supply voltage for sensors.
  • Verification of measument veracity by comparison of two connected sensors signals.
  • Individual sensor calibration capability.
  • Indication in mm or μm.
  • 2 NO relay outputs for signaling.
  • Relay operation under ‘AND’/’OR’ condition.
  • Interference and powerfailure faults protection.
  • Programmable DC-current output 0..5, 0..20 or 4..20 mA.
  • Interface RS-485, protocol Modbus (RTU).
  • Five-digit green LED display with 20 mm symbol height.

 

Technical specifications

Measuring range, mm*

0.5..10

Reduced measurement error, %

±3

DC-current output error, mA

±0.05

Supply voltage (depends on model)

220VAC 50Hz
24VDC

Sensors supply voltage

(15..28)VDC

Least significant digit value

0,01 mm or

1 μm

Operating temperature range:

  • device
  • sensor

 
+5°С..+50°С
-25°С..+70°С or

+5°С..+110°С 

Protection type (IP code):

  • device
  • sensor

 
IP41
IP67

Size (W×H×D), mm

144×74×120

* — depends on sensor type.

Eddy current displacement transducer manufactured by Vicont,  contactless inductive gap sensor manufactured by TURCK  or their analogs can be used as the sensor.

 

Scope of supply:

  • digital measuring device IP-5-TKХXХ:

ХXХ – supply voltage variants:

«24V» – 24 VDC;

no marking – 220 VAC 50Hz;

  • remote console for device setting up;
  • displacement transducer (option);
  • AC/DC converter 220VAC/24VDC (if 24VDC supply voltage variant is choosed).

   

Ordering designation

Linear and angular shift meter IK-1-TK-5.

Specify IP-5-TK model, type and quantity of displacement transducers when ordering.

ExampleLinear and angular shift meter IK-1-TK-5 composed of:

  • digital measuring device IP-5-TK-24V;
  • eddy current displacement transducer ВК-316ОС.01.