- Measuring signals from temperature sensors (resistance temperature detectors – RTD, thermocouples – TC), instrument shunts and sensors with unified current output
- Transfer measurement results over RS-485 interface, protocol Modbus (RTU).
- Three-wire or four-wire RTD connection.
- Device conversion function – linear or square-root extracting.
- Cold junction temperature compensation:
- internal sensor;
- receiving from external meter over RS-485 interface, Modbus RTU protocol
- Configurable analog input.
- Continuous sensor fault detection.
- Unified current output 0..5, 0..20 or 4..20 mA
- Five-digit green LED display with 10 mm symbol height.
- 2 optorelay for AC/DC circuits 48V/0,4A.
- Installation on DIN rail, 35 mm.
Specification
TC: |
K, L, T, S, B |
RTDs:
|
Pt50, Pt100, Pt500 Cu50, Cu100 |
Current output signal range, mA |
0..5; 0..20; 4..20 |
Baud rate, kbit/s | 9,6; 19,2; 38,4 |
Power supply | (12..24) VDC |
Operating temperature range | +5°С..+50°С |
Dust and moisture protection | IP20 |
Overall dimension (Ш×В×Д), мм | 53×98×58 |
Main measuring errors
For ТК-6-2 modification:
TC temperature measuring absolute error, °С, up to:
|
5,0 ±(0,1·10-2·|t|+0,5) ±(0,1·10-2·|t|+0,25) ±(0,05·10-2·|t|+0,2) ±(0,05·10-2·|t|+0,1) |
RTD temperature measuring absolute error, °С, up to: | ±(0,2·10-2·|t+273|+0,1) |
Unified current signal measuring reduced error, %, up to | ±0,25 |
Instrument shunts measuring reduced error, %, up to | ±0,5 |
For TK-6-2-P modification
TC temperature measuring absolute error, °С, up to:
|
5,0 ±(0,1·10-2·|t|+0,5) ±(0,1·10-2·|t|+0,25) ±(0,05·10-2·|t|+0,2) ±(0,05·10-2·|t|+0,1) |
RTD temperature measuring absolute error, °С, up to:
|
|
Unified current signal and instrument shunt measuring reduced error, %, up to | ±0,25 |
Ordering designation
Digital measuring device TK-6-2-X–Y–Z, где:
X – modification:
“P” – high precision;
no marking – standard precision.
Y – наличие интерфейса RS-485:
“R” – with RS-485;
no marking – without RS-485.
Z -наличие токового выхода:
“C” – with current output;