Измерительный преобразователь с универсальным входом ТК-6
  • Measurement and conversion of electrical signals generated by thermocouples, RTDs, bridge transducers, sensors with DC-current output.  
  • Three-wire or four-wire RTD connection.
  • Transfer measurement results over RS-485 interface, protocol Modbus (RTU).
  • Device conversion function – linear or square-root extracting.
  • Cold junction temperature compensation (internal sensor).
  • The possibility to receive the cold junction temperature from the external meter over RS-485 interface, Modbus protocol (RTU).
  • The configurable analog input.
  • Continuous sensor fault detection.
  • LED indication of operating modes.
  • Installation on DIN rail, 35 mm.

 

Technical specifications

Thermocouples K, L, S, B
RTDs:

  •  platinum (W100=1.3850 и W100=1.3910)
  •  copper (W100=1.4260 и W100=1.4280)
 

Pt50, Pt100, Pt500

Cu50, Cu100 

DC-current input signal range, mA 0..5; 0..20; 4..20
Bridge transducer input signal range, mV 0..90
Temperature measurement error (for thermocouples), °С:

  • L, K in the range of -150..0°С
  • L, K in the range of 0..800 (1300)°С
  • S
  • B

±(0.25·10-2×|t|+0.5*)
±(0.1·10-2×|t|+0.5*)
±5.0*

±7.0

Temperature measurement error (for RTDs), °С ±(0.2·10-2·(t+273)+0.1)

Reduced DC-current signal measurement error, %:

  • for input signal range 0..5 mА
  • for input signal range 0..20, 4..20 mА

 

±0.5
±0.25

Reduced bridge transducer signal measurement error, %

±0.5
Baud rate,  Kbps 9.6; 19.2; 38.4
Supply voltage

(14..32)VDC/(14..22)VAC 50Hz 

Operating temperature range +5°С..+50°С
Protection type (IP code) IP20
Size (W×H×D), mm 17,8×85×58

* – when internal sensor is used for cold junction temperature compensation it should be added 2.0 °С to error value

 

Ordering designation

Measuring transmitter  TK-6.