- Measurement of standart DC signal.
- Converting measured value into a proportional physical value.
- Indication in custom scale units.
- Two-wire, three-wire or four-wire sensor connection.
- Device conversion function – linear or square-root extracting.
- Provides supply voltage for sensor.
- Isolated and stabilized sensor power supply 2..48 VDC, 2W can be implemented on request.
- 2 NO relay outputs for signaling.
- Continuous sensor fault detection.
- Programmable DC-current output 0..5, 0..20 or 4..20 mA.
- Interface RS-485, protocol Modbus (RTU).
- Five-digit green LED display with 20 mm symbol height.
Technical specifications
Measuring ranges, mA |
0..5; 0..20; 4..20 |
Reduced measurement error, %, for device conversion function:
|
±1.0 |
DC-current output error, mA |
±0.05 |
Supply voltage (depends on model) |
220VAC 50Hz |
Sensor supply voltage (depends on model):
|
(18..36)VDC |
Power isolation between measuring circuit and sensor supply circuit:
|
no yes |
Device input resistance, Ohm |
120 |
Least significant digit value |
0.1 |
Operating temperature range |
|
Protection type (IP code) |
|
Size (W×H×D), mm |
144×74×120 |
* — nominal voltage taken from a range (2..48) VDC.
Scope of supply:
- digital measuring device IP-7-TK–ХXХ–DYY;
- remote console for device setting up;
- AC/DC converter 220VAC/24VDC (if 24VDC supply voltage variant is choosed).
Ordering designation
Digital measuring device IP-7-TK–ХXХ–DYY:
ХXХ – supply voltage variants:
«24V» – 24 VDC;
no marking – 220 VAC 50Hz;
DYY – sensor supply voltage:
«YY» – stabilized voltage taken by a customer from a range (2..48) VDC, measuring circuit is galvanically isolated from a sensor supply circuit;
no marking –unstabilized (18..36)VDC, no power isolation between measuring circuit and sensor supply circuit.
Example. Digital measuring device IP-7-TK-24V-D36 – digital measuring device with 24VDC supply voltage, 36VDC stabilized sensor supply voltage.